The Ice Rink Control System (IRCS) is designed to control and monitor ice rink facilities to insure a high quality ice surface during game-time while providing energy savings features making it possible to achieve system payback in less than two years..
Features Include:
-
Reliable Microprocessor Based System
-
Single or Dual Rink Operation
-
LCD Graphic Display with Control Keys
-
Local and Remote PC Access (Modbus, Phone & IP)
-
Detailed Logging (Trend, Alarm, Failure & User)
-
Floor and Infrared Temperature Available
-
Sequencing of Compressors
-
Condenser Staging and Chiller Setup
-
Compressor Setup and Jacket Cooling Pump
-
Temperatures and Lighting Event Setup
-
Subfloor Warming, Snow Melt Pump & Exhaust Fan
The system uses distributed methodology to control and monitor the functions required in rink operation including: refrigeration equipment control, floor temperature, subfloor warming, exhaust fan, snow melt pumps and lighting.
A facility planner provides a monthly calendar to allow the operator to schedule compressor sequencer, chiller control setpoints and lighting levels on a daily basis for a full year. The system will support the definition of event usage set-points allowing the facility manager to tailor all temperature and lighting control set-points based on event setup groups to further simplify the scheduling process.
Several options are available for controlling and monitoring of real-time data from the IRCS. The use of a PC connection allows the use of the optional PC Monitor software. The software provides a user to access real-time graphics, overview of the system, historical log viewing, graphing, and report printing along with access to all screens on the IRCS control panel.
Remote, off-site, access is also available via modem and phone line or Ethernet TCP/IP address. All the functionality available with a local PC is available from the remote location
The IRCS is a UL and cUL listed industrial control panel built to UL508A specifications.
The Ice Rink control system is available for a dual or single ice rink controller.
Downloads
Ice Rink Control System (Literature)
Ice Rink Control System (Manual)
Screen Images
Ice Rink Control System PC Monitor Screen Images
The IRCS will controlled and/or monitor the following:
Event usage setpoints
-
Allows user to setup facility based on planned activity
-
Control/Alarm/Failure setpoints configured for each event
-
Lighting level configured for each event
-
10 programmable events
Facility planner
-
Allows user to schedule events for different days and times
-
8 standard daily schedules per rink
-
Custom schedule available for each day
-
8 time slots per schedule
-
Full year of monthly schedules per rink
Control for reciprocating compressors
Sequencer control
-
Based on brine temp, floor temp or Infrared temp
-
Setpoint scheduling controlled by the facility planner
-
Separate setpoints for compressor capacity control
-
Additional first stage temperature offset and delay for starting lead compressor
-
Able to limit the number of compressors running
Condenser control for fans and pumps
-
Option for a two-speed fan
-
Pumps may be configured as two separate or primary & standby
-
Monitoring of condenser pump and fan auxiliaries with alarms
-
Condenser stage can be forced on when compressor starts
-
Condenser is disabled if no compressors are running
-
Condenser pump forced on using a thermostat
Control of one critically charged chiller with an HLS float, up to 3 pumps with auxiliaries
Monitoring and control of an emergency stop input
Monitoring of brine supply temp
Available Options
- Refrigerant leak and gas detector with alarm
-
Control for one jacket cooling pump with Manual and Automatic Modes
-
Condenser Sump LLA with additional control
-
Computation of non condensables
-
Sub slab warming using a temperature sensor and pump
-
Exhaust fan control based on temp
-
Snow melt pump control
A PC based Demo is available for Registered users on the Demo page under the Download section on this website. Registration is required prior to entering this section & web browsers must be set to accept cookies from this site.
The IRCS is available exclusively on Ice Rink Control Packages made by M&M Refrigeration .
For all other information or assistance Contact Us or submit a on-line Information Request.
|